Guest Column | November 25, 2026

Who's Watching The PLCs? Security Monitoring For Utilities Without A Full-Time Security Team

By John Funk

Power And Gas Plant Using AI Scada System On Computer Screens-GettyImages-2187983103

On a Monday morning in late July 2026, a water operator in Braham, Minnesota, noticed that the pump at the city's treatment plant wasn't running. Crews took the plant offline to troubleshoot, and the city asked its roughly 1,700 residents to conserve water while it drew on what was stored in the tower. By that afternoon, the cause was confirmed: A cyberattack had shut down the plant's operating controls. Braham turned out to be one of more than 30 Minnesota community water systems hit over the same few days.

Most small and midsize water systems will never hire a dedicated security analyst. Towns the size of Braham don't usually run security operations centers, and most utilities that size never will.

What Braham did have was an operator who knew what normal looked like. For utilities trying to monitor for threats without a full-time security team, this is a good starting point — and a stronger foundation than it might sound. 

Useful monitoring is still within reach for small utility companies that often operate on shoestring budgets; it just has to be built around the people (and those budgets) the utilities already have.

Your Operators Are Already Your First Line Of Detection

If you look back at the attacks on small water systems over the past few years, a familiar pattern starts to show up.

In November 2023, hackers linked to Iran took over a programmable logic controller (PLC) at a booster station run by the Municipal Water Authority of Aliquippa in Pennsylvania. The station set off an alarm, and staff switched to manual control. CISA later said the attackers likely got in through poor password security and a device exposed to the internet.

In September 2024, Arkansas City, Kansas, moved its water treatment facility to manual operations after an attack that, according to the city manager, took out control systems and came with a ransom demand. Fortunately, drinking water was never affected.

That brings us back to Braham, where the warning sign was a pump that had stopped pumping — a thing which shouldn’t happen, but “shouldn’t” isn’t “can never,” and which can have many potential causes other than a cyberattack.

In each case, the incident was caught by people watching the process rather than people watching the network. That is both encouraging, since operators are very good at noticing when something is off, and a little uncomfortable, because by the time a pump stops, an attacker is already inside the control system.

The practical lesson is to formalize what operators already do. Add "could this be a cyber issue?" to the troubleshooting checklist for unexplained equipment behavior. Make sure every operator knows who to call, and in what order, when the answer might be “yes.” Ask them to note the time and take a photo of the HMI screen before rebooting anything, since that small habit preserves evidence investigators will want later.

You Can't Monitor What You Don't Know Is There

The most common weaknesses in water systems aren't exotic. When the EPA released an enforcement alert in May 2024, it reported that more than 70% of the systems it had inspected since September 2023 didn't fully comply with Section 1433 of the Safe Drinking Water Act. Inspectors found default passwords that had never been changed, single logins shared by all staff, and former employees who still had access.

The July 2026 activity followed a similar script. In a joint public service announcement, the FBI and EPA warned that attackers were going after internet-facing PLCs, and that in some cases they changed network configurations and administrative credentials, leaving operators without visibility or control.

So before buying any security monitoring solutions, find out what an attacker can see. Here are a few low-cost places to start:

  • CISA's vulnerability scanning service, which is free for water and wastewater utilities and scans internet-facing systems on an ongoing basis, with regular reports on what it finds.
  • EPA's free cybersecurity assessment, which uses a checklist based on CISA's Cybersecurity Performance Goals and comes with a prioritized risk management plan.
  • A walk-down of every remote site. Write down each cellular modem, radio, and remote access tool, who installed it, and who has the login.

That last one tends to surface surprises. It's not unusual to find a modem an integrator installed years ago at a lift station, still online, with credentials nobody on current staff knows.

Watch A Short List Of Signals, Not The Noise

Small utilities that set up logging tools or sign up for security monitoring services often give up for the same reason — there are too many alerts, most of them meaningless. The way to navigate the noise is to pick a handful of signals tied to how attacks on water systems typically tend to unfold.

  • Remote access logins, especially after hours or from unfamiliar locations
  • Changes to PLC logic, setpoints, or configurations that weren't scheduled
  • New or modified accounts on HMIs, SCADA servers, and network equipment
  • Cellular modem logs, which the FBI and EPA specifically recommend enabling and reviewing
  • Lost communications with remote sites (in Plymouth, Minnesota, the July attack hit communications at two water towers and several lift stations)
  • Malware alerts on the workstations operators and contractors use to reach the SCADA network

Most of these should be quiet most of the time, but that's the point. A list that’s short enough for your staff to review every week beats a comprehensive dashboard nobody ever opens because there’s too much noise to find the signal. 

The 3 A.M. Problem

Here's the implementation challenge that trips up nearly every small utility: Even with good logging, someone has to see the alert and know what to do with it. At most systems, that "someone" is an on-call operator, a part-time IT contractor, or a city IT department that also supports the police station and the library.

Covering one seat around the clock takes several full-time people, which is out of reach for most utilities — as we mentioned earlier, they’re often running on extremely lean budgets. That's where outsourced IT security can be a lifesaver, whether the contract is through the city's existing IT provider, a managed detection and response (MDR) service, or broader cybersecurity management services. For a utility in this position, managed cybersecurity is less about handing off responsibility and more about buying some eyes on the overnight shift.

Of course, that only works if the provider understands a water system. Plenty of enterprise cybersecurity services are built for offices and hospitals, and they can misread normal SCADA polling as suspicious traffic or, worse, automatically isolate a workstation that operators need to run the plant. Before signing anything, get clear answers to a few questions:

  1. Do they monitor OT, or only IT? Managed endpoint security on office laptops is useful, but it won't tell you someone changed a setpoint.
  2. What will they do on their own? Put it in writing that no one quarantines or shuts down a control system device without an operator's approval.
  3. Who do they call, and how fast? Get the escalation list, the expected response time and an example of what that first call sounds like.
  4. What do you get each month? Reporting should be plain enough to share with a board or council without translation.

Integrators Are Vulnerable, Too

One of the more useful details in the FBI and EPA's July 2026 warning was easy to miss. Several victims had similar network setups provided by the same third parties, which let attackers repeat a working technique across multiple utilities.

That makes your integrator's remote access part of your attack surface. Ask who on their side can connect to your systems, how they do it, whether it requires multifactor authentication, and whether those sessions are logged somewhere you can see. Utilities should keep their own backup copy of PLC code in a secure location, rather than relying on the integrator to be the only one who has it.

None of this should be read as an accusation. Integrators are often the people who know your control system best. It's simply cybersecurity risk management applied to a relationship most utilities have never looked at that way.

Practice Switching To Manual

Aliquippa, Arkansas City and Braham all had one thing in common: staff who could run the system by hand. Arkansas City drew praise from security experts specifically because going to manual operations was already part of its incident response plan.

That capability shouldn't be taken for granted. Experienced operators retire, and newer staff may have spent their whole careers working through SCADA screens. Utilities should run a tabletop exercise on a cyber scenario at least once a year, and occasionally run an actual manual operations drill at a facility where it's safe to do so.

Of course, there’s a limit to being able to switch to manual control. An official in New Ulm, Minnesota, pointed out after the July attacks that if an attacker can damage a pump motor before anyone switches over, manual control can’t undo it. That's the strongest argument for an active monitoring partner — the earlier someone sees an unauthorized change, the more options the utility has.

Making Support Fit The Budget

For a board or council, the case for monitoring is easier to make in operational terms than in security terms. A week of manual operations means overtime, missed maintenance, and a lot of nervous phone calls from residents. Compared with that, a phased approach like the following looks reasonable:

  • First 30 days: Enroll in CISA scanning, request EPA's free assessment, change default passwords, and remove accounts that shouldn't exist.
  • Next 60 days: Finish the asset inventory, turn on logging for remote access tools and modems, and assign someone to review it weekly.
  • After that: Decide whether the alert volume and risk justify outside help, and if so, whether a full set of managed cybersecurity services or a narrower monitoring contract makes sense.

Braham's water plant was back online the same day. That outcome came from an attentive operator and staff who knew what to do, rather than from large security budget. The goal for every small utility is to make that kind of response a matter of process instead of luck.

John Funk is a professional writer at SevenAtoms, a B2B marketing agency, where he writes about cybersecurity, networking, and critical infrastructure. He developed this article with Red River, a technology transformation company that helps commercial, federal, state, local, and education organizations design, secure, and manage their technology.