Guest Column | November 17, 2026

Above The Flood Line: What Flood-Resistant Design Standards Mean For Water And Wastewater Utilities

By Eleni Stefania Kalapoda

Suburban tampa aerial view-GettyImages-2169331608

When floodwater recedes, the first questions are usually about buildings: how high the water rose, which floors were lost, how soon people can return. The quieter questions arrive a day later, and they belong to the utility. Why is the sewer backing up into basements three blocks from the river? Why did a pump station that stayed dry still fail? Why is a hospital that kept its lights on now waiting for potable water to be declared safe?

Those questions sit at the meeting point of two worlds that rarely sit at the same table: the standards that govern how buildings resist floods, and the networks that carry water to those buildings and wastewater away from them. For water and wastewater professionals, the most important of those standards is one many have never opened: ASCE/SEI 24, Flood Resistant Design and Construction.

A Standard That Reaches The Meter, And Beyond

ASCE/SEI 24 is the national consensus standard that sets minimum requirements for buildings and structures in flood hazard areas. It is referenced by the International Building Code, which means that, in the many jurisdictions that adopt the I-Codes, its provisions carry the force of law for new construction and substantial improvements. It works alongside the floodplain management requirements of the National Flood Insurance Program, and in several respects it is more demanding.

At its heart is a simple idea expressed with increasing precision: a design flood elevation, set at or above the base flood elevation with added freeboard that grows with the importance of the structure. Buildings are assigned a flood design class, from low-risk structures to the essential facilities a community cannot lose, and the higher the class, the higher the protection. Elevation of the lowest floor, flood-damage-resistant materials, dry and wet floodproofing, and the treatment of enclosures below the flood line all follow from that framework.

Less widely appreciated is how far the standard reaches into the utility systems that serve a building. Electrical, mechanical, plumbing, and fuel equipment must be elevated above the design flood elevation or designed to resist flood loads and remain watertight. Water supply and sanitary systems must be designed to minimize floodwater infiltration and wastewater discharge into floodwater. These are building requirements on paper. In practice, they shape the point where private plumbing becomes public infrastructure.

Where The Building Ends And The Network Begins

Consider four points of contact.

First, the service connection. A water service line that enters below the flood line, through a foundation that was never detailed to remain watertight, becomes a path for floodwater and, worse, a route for contamination when pressure drops. The building standard asks designers to treat penetrations as part of the flood-resistant envelope. Utilities that specify service entry locations, sleeves and isolation valves in their connection standards can make that requirement far easier to meet.

Second, backflow and sewer backup. When combined or sanitary sewers surcharge during a storm, the lowest fixtures in a building become the outfall of last resort. Backwater valves, ejector systems and properly elevated cleanouts are the building's defense. They are also the utility's: every basement that does not flood with sewage is a claim avoided, a public-health incident prevented and a customer relationship preserved. Recent storms in dense American cities, where intense rainfall overwhelmed drainage far from any coastline, have shown that this is not solely a coastal concern.

Third, critical equipment. Booster pumps, meters, treatment units, backflow preventers and their controls are frequently placed in basements because space there is cheap. A flood-resistant building places them above the design flood elevation or protects them in place. Hurricane Sandy in 2012 taught us that the most expensive real estate in a flood is the space just below the waterline.

Fourth, restoration. A building that is elevated and floodproofed can be reoccupied quickly, but only if water service, sewer service and the equipment that connects them can be restored with it. Utilities that understand which customers are essential facilities under the standard's flood design classes, such as hospitals, emergency operations centers and shelters, can plan restoration priorities around the same logic the building code already uses.

Three Opportunities For Closer Coordination

The connection between building standards and utility practice is not a gap to be lamented. It is an opportunity, and those who seize it first will deliver lower risk at lower cost.

The first opportunity is shared data. Building designers work from flood hazard maps and design flood elevations; utilities work from hydraulic models, asset registers, and records of where sewers have surcharged before. Bringing those datasets together, so that a designer in a known backup zone is prompted to provide a backwater valve, or a utility planner can see which new developments are raising their equipment and which are not, turns two partial pictures into one complete one.

The second opportunity is aligned specifications. Many utilities publish connection standards and design guides that predate current flood-resistant design requirements. Reviewing those documents against ASCE/SEI 24, and against the building codes adopted locally, can remove contradictions that leave designers guessing, such as meter pits required in locations the building standard would treat as below the flood line, or equipment rooms specified at grade in mapped hazard areas.

The third opportunity is the review process itself. Code officials review buildings; utilities review connections. When those reviews run in parallel without speaking to each other, even a best-intentioned flood-resistant building can be connected in a way that undermines it. A short coordination checkpoint, in which utility reviewers confirm that service entries, backflow protection and critical equipment meet both the utility's standards and the flood-resistant design provisions, costs little and saves a great deal.

The Economics Of Getting It Right

Flood-resistant design is sometimes presented as a cost imposed on development. The evidence suggests otherwise. Research for the National Institute of Building Sciences has repeatedly found that designing buildings to exceed minimum flood requirements returns several dollars in avoided losses for every dollar invested, and that adopting current codes delivers substantial savings on its own. Much of those avoided losses sit in building systems and the utility connections that serve them, precisely where water and wastewater professionals have influence.

For utilities, the return is measured in fewer emergency callouts, fewer contamination events, faster restoration, and stronger relationships with the communities they serve. For building owners, it is measured in insurance premiums, business continuity, and the value of an asset that can be reoccupied in days rather than months. These interests are not in tension. They point in the same direction.

A Shared Line To Hold

Floods do not respect the property line between a building and the street, and neither should our thinking about resilience. The design flood elevation that a structural engineer marks on a section drawing is the same line that determines whether a pump survives, whether a backwater valve holds, and whether a neighborhood's sewers carry wastewater away or bring it back.

The standards that govern flood-resistant buildings are written with care, through a consensus process that welcomes the knowledge of practitioners from every discipline. Water and wastewater professionals have much to contribute to that conversation, and much to gain from it. The more closely utilities, code officials, and designers work together above the flood line, the more confidently our communities will weather the storms below it.

Eleni Stefania Kalapoda is a New York-based architect and urban designer; she began her professional experience through collaborations with the Renzo Piano Building Workshop team on the Stavros Niarchos Foundation Cultural Center, and later worked at Foster + Partners (KSIA) and Perkins Eastman on projects at the building and city scale. She served as a sustainability expert on the RIBA Awards jury that assessed Lion Green Road, winner of the 2026 RIBA Stirling Prize, sits on the FRAME Awards Grand Jury and the Autodesk University Advisory Council, contributes to the USGBC's LEED v5 and the ASCE/SEI 24 flood-resistant design standard, and is a 2026 Beverly Willis Architecture Foundation Emerging Leaders Fellow.