909 Series Reduced Pressure Zone Backflow Pre-venters
FEATURES
AVAILABLE MODELS
Suffix:
BB - with bronze body (2 1 Ú2", 3")(64, 76mm)
LF - without shutoffs
NRS - with non-rising stem resilient wedge gate valves
OS&Y - with UL/FM resilient seated outside stem and
QT - with quarter-turn, full port, resilient seated
QT-FDA - with FDA approved epoxy coated ball valve shutoffs
S - with non-epoxy strainer
S-FDA - with FDA approved epoxy coated strainer
SPECIFICATIONS
For Reduced Pressure Zone Backflow Preventers A reduced pressure zone backflow preventer shall be installed at
each cross-connection to prevent backsiphonage and backpres-sure backflow of hazardous materials into the potable water supply. The assembly shall consist of a pressure differential re-lief valve located in a zone between two positive seating check valves and captured springs. Backsiphonage protection shall in-clude provision to admit air directly into the reduced pressure zone via a separate channel from the water discharge channel. The assembly shall include two tightly closing shutoff valves be-fore
and after the valve and test cocks. The assembly shall meet the requirements of ASSE Std.